WAGO-I/O-SYSTEM 750
750-451 8 AI RTD
4.3.15
Resistance Measurement 2, 0 Ohm ... 1.2 kOhm, ID 15
No short-circuit detection for resistance measurements!
For sensor types "Resistance measurement 1" and "Resistance measurement 2",
short-circuit detection is not technically possible.
4.3.15.1

Default Format

With the setting "Resistance measurement 2" (0 Ohm to 1.2 kOhm), the I/O
module outputs the measured resistance values of the sensors directly.
The resistance values are displayed at a resolution of 1 digit per 0.05 Ω in one
word (16-bit). The maximum number range viewable in one word in two's
complement representation ranges from −32768 to +32767. The number range
used depends on the sensor type set and the resolution of the process value. For
the setting "Resistance measurement 2", the possible numerical range
corresponds to the defined measuring range of 0 Ohm to 1.2 kOhm and ranges
from 0 to +24000 accordingly.

Table 49: ID 15, Setting "Resistance measurement 2", Standard Format

Resistance
Ω
0
100
200
300
400
500
750
1000
1200
> 1200
Overrange
> 5010
Wire break
1) When short circuit and wire break monitoring is ON (see section "Diagnostics" > „Behavior in
the Event of an Error")
2) When underrange / overrange limit is ON (see section "Diagnostics" > „Behavior in the Event of
an Error")
Binary
'0000.0000.0000.0000'
'0000.0111.1101.0000'
'0000.1111.1010.0000'
'0001.0111.0111.0000'
'0001.1111.0100.0000'
'0010.0111.0001.0000'
'0011.1010.1001.1000'
'0100.1110.0010.0000'
'0101.1101.1100.0000'
'0101.1101.1100.0000'
2)
'0101.1101.1100.0000'
1)
Numeric value
Hex.
Dec.
0x0000
0x7D0
2000
0x0FA0
4000
0x1770
6000
0x1F40
8000
0x2710
10000
0x3A98
15000
0x4E20
20000
0x5DC0
24000
0x5DC0
24000
0x5DC0
24000
Process Image
Status
Error
byte
LED
hex.
0
0x00
OFF
0x00
OFF
0x00
OFF
0x00
OFF
0x00
OFF
0x00
OFF
0x00
OFF
0x00
OFF
0x00
OFF
0x42
ON
0x60
ON
Manual
Version 1.2.0