WAGO-I/O-SYSTEM 750
750-451 8 AI RTD
4.3.11

Ni1000 (TK5000), high-resolution, ID 9

4.3.11.1

Default Format

With the setting "Ni1000 (TK5000)", the I/O module converts the measured
resistance values of Ni1000 sensors (TK5000) into temperature values and
outputs the conversion results in degrees Celsius.
The temperature values are displayed at a resolution of 1 digit per 0.01 °C in one
word (16-bit). Temperature values below 0 °C are represented in two's
complement binary. As a result, 0 °C corresponds to the numeric value 0x0000
and 100 °C to the numeric value 0x2710 (dec. 10000).
The maximum number range viewable in one word in two's complement
representation ranges from −32768 to +32767. The number range used depends
on the sensor type set and the resolution of the process value. For the setting
"Ni1000 (TK5000)", the possible numerical range corresponds to the defined
temperature range of −50 °C to +150 °C and ranges from −5000 to +15000
accordingly.

Table 41: ID 9, Setting Ni1000 (TK5000), Standard Format

Temperature
°C
---
Short circuit
< −50.0
Underrange
−50.0
−25.0
0.0
50.0
100.0
125.0
150.0
> 150.0
Overrange
---
Wire break
1) Temperature values below 0 °C are represented in two's complement binary.
2) When short circuit and wire break monitoring is ON (see section "Diagnostics" > „Behavior in
the Event of an Error")
3) When underrange / overrange limit is ON (see section "Diagnostics" > „Behavior in the Event of
an Error")
Resistance
Ω
Binary
< 10.00
'1110.1100.0111.1000'
2)
< 790.88
'1110.1100.0111.1000'
3)
790.88
'1110.1100.0111.1000'
892.47
'1111.0110.0011.1100'
1000.00
'0000.0000.0000.0000'
1234.98
'0001.0011.1000.1000'
1500.00
'0010.0111.0001.0000'
1645.10
'0011.0000.1101.0100'
1799.27
'0011.1010.1001.1000'
> 1799.27
'0011.1010.1001.1000'
3)
> 5010.00
'0011.1010.1001.1000'
2)
1)
Numeric value
Hex.
0xEC78
0xEC78
0xEC78
0xF63C
0x0000
0x1388
0x2710
0x30D4
0x3A98
0x3A98
0x3A98
Process Image
51
Status
Error
byte
LED
hex.
Dec.
−5000
0x50
ON
−5000
0x41
ON
−5000
0x00
OFF
−2500
0x00
OFF
0
0x00
OFF
5000
0x00
OFF
10000
0x00
OFF
12500
0x00
OFF
15000
0x00
OFF
15000
0x42
ON
15000
0x60
ON