60
Process Image
4.3.15.2

S5-FB250 Format

With the setting "Resistance measurement 2" (0 Ohm to 1.2 kOhm) and activated
S5-FB250 format, the I/O module outputs the measured resistance values of the
sensors directly.
The resistance values are displayed at a resolution of 1 digit per 0.5 Ohm. The
status information is depicted in bit 0 to bit 2 and the digitalized measured value
in bit 3 to bit 15.

Table 50: ID 15, Setting "Resistance measurement 2", S5-FB250 Format

Resistance
Ω
0
100
200
300
400
500
750
1000
1200
> 1200
Overrange
> 5010
Wire break
1) When short circuit and wire break monitoring is ON (see section "Diagnostics" > „Behavior in
the Event of an Error")
2) When underrange / overrange limit is ON (see section "Diagnostics" > „Behavior in the Event of
an Error")
3) Status information:
X: Not used,
F: Short circuit, wire break,
Ü: Underrange, overrange
Manual
Version 1.2.0
Numeric value with status information
Binary
'0000.0000.0000.0 000'
'0000.0110.0100.0 000'
'0000.1100.1000.0 000'
'0001.0010.1100.0 000'
'0001.1001.0000.0' 000'
'0001.1111.0100.0 000'
'0010.1110.1110.0 000'
'0011.1110.1000.0 000'
'0100.1011.0000.0 000'
'0100.1011.0000.0 001'
2)
'0100.1011.0000.0 010'
1)
WAGO-I/O-SYSTEM 750
XFÜ
Hex.
Dec.
0x0000
0x0640
1600
0x0C80
3200
0x12C0
4800
0x1900
6400
0x1F40
8000
0x2EE0
12000
0x3E80
16000
0x4B00
19200
0x4B01
19201
0x4B02
19202
750-451 8 AI RTD
Status
3)
Error
byte
LED
hex.
0
0x00
OFF
0x00
OFF
0x00
OFF
0x00
OFF
0x00
OFF
0x00
OFF
0x00
OFF
0x00
OFF
0x00
OFF
0x42
ON
0x60
ON