26
Device Description
3.6.6

Connection Type

Table 15: Technical Data ‒ Field Wiring
Wire connection
Cross section, solid wire
Cross section, fine-stranded wire
Stripped lengths
Table 16: Technical Data – Power Jumper Contacts
Power jumper contacts
Table 17: Technical Data – Data Contacts
Data contacts
3.6.7

Climatic Environmental Conditions

Table 18: Technical Data – Climatic Environmental Conditions
Surrounding air temperature
(operation)
Surrounding air temperature
(operation) for components with
extended temperature range
(750-xxx/025-xxx)
Surrounding air temperature (storage) −25 °C ... +85 °C
Surrounding air temperature (storage)
for components with extended
temperature range (750-xxx/025-xxx)
Operating altitude
Relative humidity
Pollution degree
Protection type
Resistance to harmful substances
Maximum pollutant concentration at
relative humidity < 75 %
Special conditions
Manual
Version 1.2.0
WAGO-I/O-SYSTEM 750
Push-in CAGE CLAMP
0.08 mm² ... 1.5 mm² / AWG 28 ... 16
0.25 mm² ... 1.5 mm² / AWG 22 ... 16
8 mm ... 9 mm / 0.33 in
Blade/spring contact, self-cleaning
Slide contact, hard gold plated, self-
cleaning
0 °C ... 55 °C
−20 °C ... +60 °C
−40 °C ... +85 °C
without temperature derating:
0 ... 2000 m;
with temperature derating:
2000 ... 5000 m (0.5 K/100 m);
max.: 5000 m
Max. 5 % ... 95 % without condensation
2
IP20
Acc. to IEC 60068-2-42 and
IEC 60068-2-43
SO
≤ 25 ppm
2
H
S ≤ 10 ppm
2
Ensure that additional measures for
components are taken, which are used in
an environment involving:
– dust, caustic vapors or gases
– ionizing radiation
750-451 8 AI RTD
®