S5-FB250 Format

With the setting "Resistance measurement 1" (0 Ohm to 5.0 kOhm) and activated
S5-FB250 format, the I/O module outputs the measured resistance values of the
sensors directly.
The resistance values are displayed at a resolution of 1 digit per 4 Ohm. The
status information is depicted in bit 0 to bit 2 and the digitalized measured value
in bit 3 to bit 15.

Table 48: ID 14, Setting "Resistance measurement 1", S5-FB250 Format

Resistance
Ω
0
100
200
300
1000
2000
3000
4000
5000
> 5000
Overrange
> 5010
Wire break
1) When short circuit and wire break monitoring is ON (see section "Diagnostics" > „Behavior in
the Event of an Error")
2) When underrange / overrange limit is ON (see section "Diagnostics" > „Behavior in the Event of
an Error")
3) Status information:
X: Not used,
F: Short circuit, wire break,
Ü: Underrange, overrange
Manual
Version 1.2.0
Numeric value with status information
Binary
'0000.0000.0000.0 000'
'0000.0000.1100.1 000'
'0000.0001.1001.0 000'
'0000.0010.0101.1 000'
'0000.0111.1101.0 000'
'0000.1111.1010.0 000'
'0001.0111.0111.0 000'
'0001.1111.0100.0 000'
'0010.0111.0001.0 000'
'0010.0111.0001.0 001'
2)
'0010.0111.0001.0 010'
1)
WAGO-I/O-SYSTEM 750
XFÜ
Hex.
Dec.
0x0000
0x00C8
200
0x0190
400
0x0258
600
0x07D0
2000
0x0FA0
4000
0x1770
6000
0x1F40
8000
0x2710
10000
0x2711
10001
0x2712
10002
750-451 8 AI RTD
Status
3)
Error
byte
LED
hex.
0
0x00
OFF
0x00
OFF
0x00
OFF
0x00
OFF
0x00
OFF
0x00
OFF
0x00
OFF
0x00
OFF
0x00
OFF
0x42
ON
0x60
ON