"Module" Menu Item - WAGO 750-451 Manual [Page 75]">
Download Table of Contents Contents Print this page

Table 55: "Settings" > "Module" Menu Item - WAGO 750-451 Manual

8-channel analog input module for resistance sensors for wago-i/o-system 750
Hide thumbs Also See for 750-451:
Table of Contents

Advertisement

WAGO-I/O-SYSTEM 750
750-451 8 AI RTD
Table 55: "Settings" > "Module" Menu Item
Option
Formatting of process values
Number format
Use SIEMENS S5 format 
Watchdog Timer
Disable Watchdog timer
Filter selection
disabled
50 Hz
60 Hz
50/60 Hz
Changing the process value resolution in Siemens S5 format!
The resolution of the process value is changed by enabling SIEMENS S5 format.
Specific information about resolutions is available in chapter "Process Data" >
"Overview of Sensor Types".
The settings for each individual channel can be made under the "Channel 1" to
"Channel 8" menu items in the navigation area. The setting options for each
channel are identical. Therefore, the description of "Channel 1" menu item is
representative of all channels.
Description
Two's complement representation
Amount/sign representation
The SIEMENS S5 format is enabled. Display of status indicators
in the bottom three bits:
Bit 0:
Overflow. Set for
overrange/underran
ge (if
overrange/underran
ge is enabled)
The SIEMENS S5 format is disabled. No display of status
indicators.
The "Disable Watchdog timer" option is enabled. The green
LEDs illuminate continuously.
The "Disable Watchdog timer" option is disabled. If no process
data is exchange with the bus coupler for 100 ms, the green
LEDs go out.
The Notch filter is disabled.
The Notch filter is disabled (50 Hz)
The Notch filter is disabled (60 Hz)
The Notch filter is disabled (50/60 Hz)
Commissioning
Bit 1: Error. Set for
Bit 2: Always 0.
wire break/short
circuit (if "Indicate
wire break/short
circuit" is enabled).
75