Advertisement

5.
Set 'CH1 D/A conversion enable/disable setting' (Un\G500) to D/A conversion enable (0).
6.
Turn on and off 'Operating condition setting request' (Y9).
7.
Turn on 'CH1 Output enable/disable flag' (Y1).
8.
Start wave output by setting 'CH1 Wave output start/stop request' (Un\G462) to Wave output start request (1). Then the
values are output in analog as shown below.
Analog output
20μs 20μs
5V
0V