Initial settings of the wave output function

For the wave output function, set the following items as the initial setting. Before using the wave output function, complete the
procedures described in this section.
• Creating wave data (Page 52 Creating wave data)
• Setting parameters of the wave output function (Page 56 Setting parameters of the wave output function)
• Writing wave output data to a file register (ZR) or CSV file (Page 57 Writing data to a file register (ZR) or CSV file)
• Setting parameters of D/A converter module (Page 58 D/A conversion enable/disable setting)
Creating wave data
Create the wave data in "Create Wave Output Data" window of the engineering tool.
1.
Start "Create Wave Output Data".
[Tool]  [Module Tool List]  [Analog Output]  [Create wave output data]
2.
Select "R60DAH4" in "Module Type".
If the type other than "R60DAH4" is selected, proper wave data cannot be created because a corresponding
channel or a range of digital values differs.
In addition, the wave pattern and the wave output data are completely deleted by changing "Module Type".
Therefore, set the correct value in "Module Type" and follow the step 3 and later.
3.
Select the graph displayed in "Register wave pattern" and press the [Enter] key on the keyboard. The "Register wave
pattern" window is displayed.
4.
Set "Wave pattern information".
Item
Wave pattern No.
Wave pattern name
Digital value range
Number of data
Comments
5.
Click any position on the wave graph to create an end point. The created end point is displayed with
The end point that can be created is up to 360. No points can be added if there are 360 points.
1 FUNCTIONS
52
1.14 Wave Output Function
Description
The wave pattern number selected in the "Create Wave Output Data" window
is displayed. Up to 10 wave patterns can be created.
Set the name of the wave pattern.
Select the setting range of the digital value according to the output range to be
used.
Set the number of the digital values of the wave pattern.
Set the comment of the wave pattern.
Created end point
Setting range
16 characters
• 0 to 32000 (default value)
• -32000 to 32000
1 to 90000 (default value: 100)
64 characters
.