1.2

Range Switching Function

Common
This function allows switching the output range of an analog output for each channel.
Switching the range makes it possible to change the I/O conversion characteristic.
Operation
The set digital value is converted to an analog value within the analog output range of the output range set in "Output range
setting" and the analog value is output.
The digital value used in the D/A conversion varies depending on the operation mode.
• High-speed output mode, normal output mode: 'CH1 Digital value' (Un\G460)
• Wave output mode: Wave data registry area (Un\G10000 to Un\G99999)
• Inter-module synchronization mode: 'CH1 Synchronization digital value' (Un\G9500)
Setting method
Set the output range to be used in "Output range setting".
[Navigation window]  [Parameter]  [Module Information]  Module model name  [Basic setting]  [Range
switching function]
Output range setting
4 to 20mA
0 to 20mA
1 to 5V
0 to 5V
-10 to 10V
User range setting (voltage)
User range setting (current)
The range can be switched or the set range can be monitored in the following buffer memory areas.
• 'CH1 Range setting' (Un\G598)
• 'CH1 Range setting monitor' (Un\G430)
For details on the buffer memory areas, refer to the following.
Page 178 CH1 Range setting
Page 163 CH1 Range setting monitor
1 FUNCTIONS
20
1.2 Range Switching Function
Digital input range
0 to 32000
0 to 32000
-32000 to 32000
-32000 to 32000
-32000 to 32000