Mitsubishi Electric MELSEC iQ-R Series User Manual page 172

High speed digital-analog converter module
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

CH1 Scaling upper limit value
Normal
Set an upper limit value for the range of the scale conversion.
For details on the scaling function, refer to the following.
Page 28 Scaling Function
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory name
CH Scaling upper limit value
■Setting range
• The setting range is from -32000 to 32000.
• In the channel where a value out of the range is set, a scaling setting range error (error code: 1A1H) occurs.
• In the channel where a set value does not satisfy the condition "the scaling upper limit value  the scaling lower limit value",
a scaling upper/lower limit value setting error (error code: 1A2H) occurs.
• When 'CH1 Scaling enable/disable setting' (Un\G502) is set to Disable (1), the setting for 'CH1 Scaling upper limit value'
(Un\G504) is ignored.
■Enabling the setting
Turn on and off 'Operating condition setting request' (Y9).
■Default value
The default value is 0 for all channels.
CH1 Scaling lower limit value
Normal
Set a lower limit value for the range of the scale conversion.
For details on the scaling function, refer to the following.
Page 28 Scaling Function
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory name
CH Scaling lower limit value
■Setting range
• The setting range is from -32000 to 32000.
• In the channel where a value out of the range is set, a scaling setting range error (error code: 1A1H) occurs.
• In the channel where a set value does not satisfy the condition "the scaling upper limit value  the scaling lower limit value",
a scaling upper/lower limit value setting error (error code: 1A2H) occurs.
• When 'CH1 Scaling enable/disable setting' (Un\G502) is set to Disable (1), the setting for 'CH1 Scaling lower limit value'
(Un\G506) is ignored.
■Enabling the setting
Turn on and off 'Operating condition setting request' (Y9).
■Default value
The default value is 0 for all channels.
APPX
170
Appendix 3 Buffer Memory Areas
CH1
CH2
504
704
CH1
CH2
506
706
CH3
CH4
904
1104
CH3
CH4
906
1106