Starting/stopping/pausing wave output
■Starting the wave output
The wave output can be started by the following procedures after the wave data registration.
1.
Turn on 'CH1 Output enable/disable flag' (Y1).
The value is output in analog according to the setting in 'CH1 Output setting during wave output stop' (Un\G524).
2.
Set 'CH1 Wave output start/stop request' (Un\G462) to Wave output start request (1).
When Wave output stop request (0) or Wave output pause request (2) is changed to Wave output start request (1), the wave
output is started.
■Stopping the wave output
To stop the wave output at a desired timing during the wave output, set 'CH1 Wave output start/stop request' (Un\G462) to
Wave output stop request (0). When Wave output start request (1) or Wave output pause request (2) is changed to Wave
output stop request (0), the wave output is completely stopped. When the wave output is stopped, During wave output stop (0)
is stored in 'CH1 Wave output status monitor' (Un\G401)'. The wave output cannot be restarted at the stop point.
When the wave pattern outputs for the count set in 'CH1 Wave pattern output repetition setting' (Un\G530) are finished, the
wave output is also stopped.
CPU module status
'CH1 D/A conversion
enable/disable
setting' (Un\G500)
'CH1 Output enable/disable
flag' (Y1)
'CH1 Wave output start/stop
request' (Un\G462)
'CH1 Wave output status
monitor' (Un\G401)
Wave data
Output according to the setting of
'CH1 Output setting during wave
output stop' (Un\G524)
(1) Setting 'CH1 Wave output start/stop request' (Un\G462) to Wave output start request (1) starts the wave output.
(2) The wave output ends.
(3) To execute the wave output again, change 'CH1 Wave output start/stop request' (Un\G462) to Wave output stop request (0), and then change it to Wave
output start request (1).
(4) During the wave output, setting 'CH1 Wave output start/stop request' (Un\G462) to Wave output stop request (0) stops the wave output.
1 FUNCTIONS
60
1.14 Wave Output Function
OFF
Wave output stop
Wave output start
request (0)
request (1)
During wave
output stop (0)
Analog output
Offset value
RUN
D/A conversion enable (0)
(3)
3)
ON
Wave output stop
request (0)
During wave
output stop (0)
During wave
output (1)
(2)
(1)
Wave output
start request (1)
Wave output stop
request (0)
During wave
output stop (0)
(4)