Mitsubishi Electric MELSEC iQ-R Series User Manual page 31

High speed digital-analog converter module
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

Setting method
1.
Set "Scaling enable/disable setting" to "Enable".
[Navigation window]  [Parameter]  [Module Information]  Module model name  [Application setting]  [Scaling
function]
2.
Set values for "Scaling upper limit value" and "Scaling lower limit value".
Item
Scaling upper limit value
Scaling lower limit value
Setting example of scaling
Ex.
When 14000 is set to the scaling upper limit value and 4000 is set to the scaling lower limit value for the channel with the
output range of 0 to 5V
Analog output voltage (V)
5
0
0
S
: 4000
L
S
: Scaling upper limit value
H
S
: Scaling lower limit value
L
Digital value
4000
6000
8000
10000
12000
14000
Digital value
32000
S
: 14000
H
Digital value after scaling
0
6400
12800
19200
25600
32000
Setting range
-32000 to 32000
Analog output voltage (V)
0
1
2
3
4
5
1 FUNCTIONS
29
1.7 Scaling Function
1

Advertisement

Table of Contents
loading

This manual is also suitable for:

R60dah4

Table of Contents