CH1 Wave pattern data points setting
Wave
This area is for setting the points of the wave pattern to be output. From the start address of the wave pattern, the D/A
conversion starts for the points of wave data set in this area and the converted analog values are output.
For this area, set a value in 32-bit signed binary.
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory name
CH Wave pattern data points setting
■Setting range
• The setting range is from 1 to 90000. A number of data points corresponding to that of Wave data registry area (Un\G10000
to Un\G99999) can be set.
• In the channel where a value out of the setting range is set, a wave pattern data points setting range error (error code:
1D5H) occurs. The wave output does not start. However, when the value of 'CH1 Wave pattern start address setting'
(Un\G526, Un\G527) is outside the setting range, the above error does not occur.
• Set the value so that the setting value in this area + 'CH1 Wave pattern start address setting' (Un\G526, Un\G527) - 1 is
99999 (the last address of wave data registry area) or less. In the channel where the value is over 99999, a wave data
registry area setting range error (error code: 1D9H) occurs. The wave output does not start.
■Enabling the setting
Turn on and off 'Operating condition setting request' (Y9) to enable the setting.
■Default value
The default value is 0 for all channels.
CH1 Wave pattern output repetition setting
Wave
This area is for setting the repeat count to output the wave pattern repeatedly.
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory name
CH Wave pattern output repetition setting
■Setting range
• Follow the setting range below.
Setting value
-1
1 to 32767
• In the channel where a value out of the setting range is set, a wave pattern output repetition setting range error (error code:
1D6H) occurs. The wave output does not start.
■Enabling the setting
Turn on and off 'Operating condition setting request' (Y9) to enable the setting.
■Default value
The default value is 1 (time) for all channels.
CH1
528, 529
CH1
530
Description
The wave pattern is output in analog unlimitedly.
The wave pattern is output in analog for the counts of the setting value.