Operation mode transition
The following figure and table describe the transition condition for each operation mode.
(7)
Inter-module
synchronization
mode
No.
Transition condition
*1
(1)
Set "High speed output mode (1s/CH)" for "Operation mode setting" in "Basic setting" of the engineering tool.
(2)
Set "Normal output mode (10s/CH)" for "Operation mode setting" in "Basic setting" of the engineering tool.
*1
(3)
Set "Wave output mode (20s/CH)" for "Operation mode setting" in "Basic setting" of the engineering tool.
(4)
Set "Offset/gain setting mode" for "Operation mode setting" in "Basic setting" of the engineering tool.
(5)
Change the mode with one of the following methods.
Method 1
Method 2
(6)
Change the mode with one of the following methods.
Method 1
Method 2
*1*2
(7)
Set "Synchronize" for the D/A converter module in the following parameter of the engineering tool.
[System Parameter]  [Inter-module Synchronization Setting]  [Inter-module Synchronization Setting]  [Select Inter-module
Synchronization Target Module]
*1 The high-speed output mode, wave output mode, and inter-module synchronization mode are independent from the other modes. After
the module is started in the high-speed output mode, wave output mode, or the inter-module synchronization mode, the mode cannot be
changed to the other operation modes. After the module is started in a mode other than the three modes, the mode cannot be switched
to the high-speed output mode, wave output mode, and inter-module synchronization mode.
*2 When "Synchronize" is set for the D/A converter module in "Select Inter-module Synchronization Target Module", the module operates in
the inter-module synchronization mode regardless of "Operation mode setting". To operate the module in the high-speed output mode,
normal output mode, wave output mode, or offset/gain setting mode, set "Do Not Synchronize" for the D/A converter module in "Select
Inter-module Synchronization Target Module".
1 FUNCTIONS
18
1.1 Modes
At power-on or at reset
of the CPU module
(3)
Wave output
mode
Execute the G(P).OFFGAN (argument "S": 0: Shifting to the normal output mode).
Set the following values for 'Mode switching setting' (Un\G296, Un\G297) and turn on and off 'Operating condition
setting request' (Y9).
• Un\G296: 5260H
• Un\G297: 4441H
Execute the G(P).OFFGAN (argument "S": 1: Shifting to the offset/gain setting mode).
Set the following values for 'Mode switching setting' (Un\G296, Un\G297) and turn on and off 'Operating condition
setting request' (Y9).
• Un\G296: 4441H
• Un\G297: 5260H
(2)
(1)
High-speed
output mode
(4)
Offset/gain
setting mode
(6)
Normal output
mode