Operation example of the rate control function
The following figure and table show an operation example when the rate control function is used for CH1 to CH3.
Setting item
D/A conversion enable/disable setting
Rate control enable/disable setting
Increase digital limit value
Digital value
The increments of the analog output value by conversion cycle for each channel with the above settings are as follows:
• CH1: 4500 (CH1 Increase digital limit value Number of D/A conversion enabled channels)
• CH2: 3000 (CH2 Increase digital limit value Number of D/A conversion enabled channels)
• CH3: 1500 (CH3 Increase digital limit value Number of D/A conversion enabled channels)
(Analog output)
<CH1>
1.25V
Change of the internal
digital value
<CH2>
1.25V
Change of the internal
digital value
<CH3>
1.25V
Change of the internal
digital value
(Channel for the conversion)
(Buffer memory)
'CH1 Digital value'
(Un\G460)
'CH2 Digital value'
(Un\G660)
'CH3 Digital value'
(Un\G860)
1 FUNCTIONS
36
1.10 Rate Control Function
CH1 setting
Enable
Enable
1500
Changed from 4000 to
16000
V
5V
4000
8500
13000
Difference
+4500
+4500
between
the changes
V
5V
4000
7000
Difference
+3000
+3000
between
the changes
V
5V
4000
5500
Difference
+1500
+1500
between
the changes
2 3
1 2 3
1 2 3
1 2 3
Conversion speed = 10μs
Conversion cycle = 30μs
4000 (1.25V)
4000 (1.25V)
4000 (1.25V)
CH2 setting
Enable
Enable
1000
Changed from 4000 to
16000
16000
+3000
10000
13000
16000
+3000
+3000
7000
8500
10000
11500
+1500
+1500
+1500
1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2
16000 (5.0V)
16000 (5.0V)
16000 (5.0V)
CH3 setting
Enable
Enable
500
Changed from 4000 to
16000
t
t
t
13000
14500
16000
+1500
+1500
+1500
CH4 setting
Disable
Disable