CH1 Warning output upper limit value
Normal
Set an upper limit of digital value to output warnings.
For details on the warning output function, refer to the following.
Page 33 Warning Output Function
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory name
CH Warning output upper limit value
■Setting range
• The setting range is from -32768 to 32767.
• Set the values that satisfy the condition "warning output upper limit value > warning output lower limit value". In the channel
where a set value does not satisfy the condition, a warning output upper/lower limit value inversion error (error code:
1B1H) occurs.
• When 'CH1 Warning output setting' (Un\G508) is set to Disable (1), the setting of 'CH1 Warning output upper limit value'
(Un\G510) is ignored.
■Enabling the setting
Turn on and off 'Operating condition setting request' (Y9).
■Default value
The default value is 0 for all channels.
■Precautions
When the shift function is used, always set a value in consideration of 'CH1 Input value shift amount' (Un\G480).
CH1 Warning output lower limit value
Normal
Set a lower limit of digital value to output warnings.
For details on the warning output function, refer to the following.
Page 33 Warning Output Function
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory name
CH Warning output lower limit value
■Setting range
• The setting range is from -32768 to 32767.
• Set the values that satisfy the condition "warning output upper limit value > warning output lower limit value". In the channel
where a set value does not satisfy the condition, a warning output upper/lower limit value inversion error (error code:
1B1H) occurs.
• When 'CH1 Warning output setting' (Un\G508) is set to Disable (1), the setting of 'CH1 Warning output lower limit value'
(Un\G512) is ignored.
■Enabling the setting
Turn on and off 'Operating condition setting request' (Y9).
■Default value
The default value is 0 for all channels.
■Precautions
When the shift function is used, always set a value in consideration of 'CH1 Input value shift amount' (Un\G480).
APPX
172
Appendix 3 Buffer Memory Areas
Wave
Synchronization
CH1
510
Wave
Synchronization
CH1
512
CH2
CH3
710
910
CH2
CH3
712
912
CH4
1110
CH4
1112

Advertisement

Table of Contents
loading

This manual is also suitable for:

R60dah4

Table of Contents