X500 Drive-Cliq Interface; X520 Encoder System Interface - Siemens SINAMICS S120 Combi Manual

Power modules
Hide thumbs Also See for SINAMICS S120 Combi:
Table of Contents

Advertisement

Encoder system connection
10.2 Sensor Module Cabinet-Mounted SMC30
10.2.2.2

X500 DRIVE-CLiQ interface

Table 10- 6
Connector type
The blanking cover for the DRIVE-CLiQ port is included in the scope of delivery.
Blanking covers (50 x) Article number: 6SL3066-4CA00-0AA0
10.2.2.3

X520 encoder system interface

Table 10- 7
X520: Encoder system interface
Pin
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
Connector type:
15-pin Sub-D socket
Measuring current via temperature sensor connection: 2 mA
Accuracy of the temperature measurement:
1)
- KTY: ±7 °C (including evaluation)
- PT1000: ±5 °C (PT1000 tolerance class B according to DIN EN 60751 including evaluation)
- PTC: ±5 °C (including evaluation)
236
X500: DRIVE-CLiQ interface
Pin
Signal name
1
TXP
2
TXN
3
RXP
4
Reserved, do not use
5
Reserved, do not use
6
RXN
7
Reserved, do not use
8
Reserved, do not use
A
Reserved, do not use
B
M (0 V)
DRIVE-CLiQ socket
Signal name
+Temp
1)
Clock
Clock*
P encoder 5 V / 24 V
P encoder 5 V / 24 V
P sense
M encoder (M)
-Temp
1)
M sense
R
R*
B*
B
A* / data*
A / data
Technical data
Transmit data +
Transmit data -
Receive data +
Receive data -
Electronics ground
Technical data
Temperature sensor KTY84-1C130 / PT1000 / PTC
SSI clock
Inverse SSI clock
Encoder power supply
Sense input of encoder power supply
Ground for encoder power supply
Temperature sensor KTY84-1C130 / PT1000 / PTC
Ground sense input
Reference signal R
Inverse reference signal R
Inverse incremental signal B
Incremental signal B
Inverted incremental signal A/inverted SSI data
Incremental signal A/SSI data
Manual, 11/2017, 6SL3097-4AV00-0BP7
SINAMICS S120 Combi

Advertisement

Table of Contents
loading

Table of Contents