Power Losses For S120 Combi Power Modules; Power Loss For Line Filters And Line Reactors - Siemens SINAMICS S120 Combi Manual

Power modules
Hide thumbs Also See for SINAMICS S120 Combi:
Table of Contents

Advertisement

12.8.4.3

Power losses for S120 Combi Power Modules

Power losses in rated operation
The following table provides an overview of the internal and external losses of the S120
Combi Power Modules for rated operation.
Table 12- 18 Overview of power losses in rated operation for S120 Combi Power Modules
S120 Combi 3 axes Power Module
16 kW / 18 A / 5 A / 5 A
16 kW / 24 A / 9 A / 9 A
20 kW / 30 A / 9 A / 9 A
S120 Combi 4 axes Power Module
10 kW / 24 A / 12 A / 12 A /
12 A
16 kW / 18 A / 9 A / 5 A / 5 A W
16 kW / 24 A / 9 A / 9 A / 9 A W
20 kW / 30 A / 12 A / 9 A /
9 A
The external fan unit has been taken into account in the specified power losses
1)
12.8.4.4

Power loss for line filters and line reactors

Table 12- 19 Overview of power loss during rated operation for line filters and line reactors
Line filter
10 kW
16 kW
20 kW
Line reactors
10 kW
16 kW
20 kW
SINAMICS S120 Combi
Manual, 11/2017, 6SL3097-4AV00-0BP7
Unit
Internal
power loss
W
81
W
91
W
102
W
115
87
100
W
113
Unit
W
W
W
W
W
W
Cabinet design and EMC
12.8 Note on control cabinet cooling
External power
Total
loss
power loss
344
425
446
537
532
634
655
770
405
492
507
607
620
733
Power loss
12
15
16
55
75
98
1)
301

Advertisement

Table of Contents
loading