X11 Brake Connection; X12/X13 Fan Connection - Siemens SINAMICS S120 Combi Manual

Power modules
Hide thumbs Also See for SINAMICS S120 Combi:
Table of Contents

Advertisement

S120 Combi Power Modules
4.3 Interface description
4.3.4

X11 brake connection

Table 4- 8
Brake connection X11
Terminal
Connectors:
BR +
BR -
Electric shock due to a terminal voltage that has not been adjusted
Contact with live terminals can cause death or severe injury.
• Only connect protective extra-low voltages (PELV or SELV) to all connections and
• Observe the voltage tolerances of the motor holding brakes (24 V ± 10%).
Note
The motor brake must be connected via connector X11. The BR- cable must not be
connected directly to electronics ground (M).
4.3.5

X12/X13 fan connection

Table 4- 9
X12/X13 connection of the external fan unit
Terminal
1
2
3
4
74
Designation
Brake connection +
Brake connection -
WARNING
terminals between 0 and 48 VDC.
Designation
Ground
Fan monitoring
+24 V
Ground
Technical specifications
Voltage: 24 VDC
Max. load current: 1 A
Minimum load current: 0.1 A
Type: Spring-loaded terminal 1 (Page 288)
The brake connector is part of the prefabricated cable.
Technical specifications
Current-carrying capacity (24 V): 2 x 1 A or 1 x 2 A
Type: Screw terminal 1 (Page 288)
Manual, 11/2017, 6SL3097-4AV00-0BP7