9.1.3.6

X522 fail-safe digital inputs

Table 9- 6
X522: Fail-safe digital inputs
Terminal
1
2
3
4
5
6
7
8
9
10
An F-DI consists of a digital input and a 2nd digital input where, in addition, the cathode of the optocoupler is fed-out.
F-DI 2 = terminals 1, 2 and 7
F-DI 3 = terminals 3, 4 and 8
F-DI 4 = terminals 5, 6 and 9
Type: Screw terminal 1 (Page 288)
DI: Digital input, F-DI: Fail-safe digital input
1)
Pure hardware delay
2)
Note
Execution of a test stop
The test stop of the F-DI 0 to F-DI 4 can only be performed if the F-DI is supplied from L1+.
Note
Ensuring the function of digital inputs
For the digital inputs DIx+ to function, the reference potential must be connected to input
DIx- in each case.
This is achieved by using one of the following measures:
1. Providing the ground reference of the digital inputs
2. A jumper between DIx- and terminal M1
SINAMICS S120 Combi
Manual, 11/2017, 6SL3097-4AV00-0BP7
Designation
1)
DI 4
F-DI 2
DI 5+
DI 6
F-DI 3
DI 7+
DI 8
F-DI 4
DI 9+
DI 5-
F-DI 2
DI 7-
F-DI 3
DI 9-
F-DI 4
M1
Additional system components
9.1 Terminal Module TM54F
Technical specifications
Voltage: -3 ... +30 VDC
Electrical isolation: Yes
Reference potential: see terminals 7, 8, 9, 10
Input characteristic acc. to IEC 61131-2, type 1
Input voltage (including ripple)
"1" signal: 15 ... 30 V
"0" signal: -3 ... +5 V
Input current
at 24 VDC: Typical 3.2 mA
for "1" signal: > 0.5 mA
Input delay:
2)
for "0" → "1": Typical 30 μs
for "1" → "0": Typical 60 μs
Switching frequency: Maximum 100 Hz
Reference potential for DI 5+
Reference potential for DI 7+
Reference potential for DI 9+
Reference potential for DI 4, DI 6 and DI 8