Typical 24 V Current Consumption Of The Components - Siemens SINAMICS S120 Combi Manual

Power modules
Hide thumbs Also See for SINAMICS S120 Combi:
Table of Contents

Advertisement

Cabinet design and EMC
12.4 24 V DC supply
Table 12- 1
Core cross-section
1.5 mm
2.5 mm
4 mm
6 mm
24 V busbar
The tripping characteristic of the miniature circuit breakers must be selected to match the
loads to be protected and the maximum current provided by the supply unit in the event of a
short circuit.
12.4.4

Typical 24 V current consumption of the components

A separate 24 V power supply must be used for the SINAMICS S120 drive group.
The following table can be used to calculate the 24 V DC power supply. The values for
typical current consumption are used as a basis for configuration.
Table 12- 2
Overview of 24 V DC current consumption
Component
Controller
SINUMERIK 828D - PPU without load
SINUMERIK 828D - PPU with full load (USB, handwheel, ...)
SINUMERIK NCU 710.3 PN without load
SINUMERIK NCU 710.3 PN with full load
Sensor Modules
SMC20
without/with encoder system
SMC30
without/with encoder system
SME20
without/with encoder system
SME25
without/with encoder system
Terminal Modules
TM54F (without digital outputs, without DRIVE-CLiQ)
Per digital output/DRIVE-CLiQ
Additional system components
DMC20 (without DRIVE-CLiQ)
per DRIVE-CLiQ
DME20 (without DRIVE-CLiQ)
per DRIVE-CLiQ
280
MCBs by core cross-section and temperature
2
2
2
2
Max. value up to 40° C
10 A
16 A
25 A
32 A
20 A
Typical current consumption [A
1.2
2.5
0.9
11.7
0.20 / 0.355
0.20 / 0.55
0.15 / 0.25
0.15 / 0.25
0.2
0.5
0.15
0.5
0.15
0.5
Max. value up to 55° C
6 A
10 A
16 A
20 A
20 A
]
DC
SINAMICS S120 Combi
Manual, 11/2017, 6SL3097-4AV00-0BP7

Advertisement

Table of Contents
loading

Table of Contents