Power Supply Wiring; Examples Of Dc Power Supply Wiring - Mitsubishi Electric FX5UC-96MT/D User Manual

Melsec iq-f fx5uc series
Hide thumbs Also See for FX5UC-96MT/D:
Table of Contents

Advertisement

6.4

Power Supply Wiring

Examples of DC power supply wiring

Provide a 24 V DC power supply to FX5UC CPU module and other modules. Use dedicated connectors to provide the power
supply. (Refer to Page 86 Connection of power cables.)
Power supply wiring example of FX5UC-32MT/D
FX5-4DA-ADP
FX5UC-32MT/D
FX5-C32EX/D
FX5-C32ET/D
FX5-C1PS-5V
FX5-C32EYT/D
FX5-CNV-IFC
S/S
FX5-16EX/ES
*1 The grounding resistance should be 100  or less.
*2 Using the same power supply to each module and extension adapters is recommended. When a different power supply is used to them,
turn on the power supply at the same time with the CPU module or earlier than the CPU module. When tuning off the power, confirm the
safety of the system and turn off the CPU module at the same time. Some extension modules may not have power supply terminals.
6 WIRING
96
6.4 Power Supply Wiring
*2
*2
Class D
*1
grounding
Power
connector
*2
Power
crossover
connector
Fuse
*2
Power supply for loads connected
*2
to PLC output terminals
For details of the emergency stop operation,
refer to "DESIGN PRECAUTIONS".
24 V DC
Circuit
protector
Power ON
PL
MC
MC
Emergency
stop
MC
MC
24 V DC
24 V DC

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents