Table 73: Parameter Channel Address 0; Table 74: Parameter Channel Address 1 - WAGO -I/O-SYSTEM 750 Manual

2/4 ai rtd configurable 2-/4-channel analog input module for rtds
Hide thumbs Also See for WAGO-I/O-SYSTEM 750:
Table of Contents

Advertisement

WAGO-I/O-SYSTEM 750
750-464 2/4 AI RTD configurable

Table 73: Parameter Channel Address 0

Parameter
channel
address
0
Bit 0: 2/4-channel switching
*)
0
4-channel operation is switched on.
1
2-channel operation is switched on.
Bit 1: 2/3-wire switching channel 1
*)
0
2-wire operation for channel 1 is switched on.
1
3-wire operation for channel 1 is switched on.
Bit 2: 2/3-wire switching channel 2
*)
0
2-wire operation for channel 2 is switched on.
1
3-wire operation for channel 2 is switched on.
Bit 3: 2/3-wire switching channel 3
*)
0
2-wire operation for channel 3 is switched on.
1
3-wire operation for channel 3 is switched on.
Bit 4: 2/3-wire switching channel 4
*)
0
2-wire operation for channel 4 is switched on.
1
3-wire operation for channel 4 is switched on.
Bit 5 ... 15: reserved
0*
These bits are reserved and may not be changed.
*)
Default settings

Table 74: Parameter Channel Address 1

Parameter
channel
address
1
Bit 0 ... 3: Sensor type channel 1
0 ... 15 See registration assignment, register 32, bit 12 ... 15
Bit 4 ... 7: Sensor type channel 2
0 ... 15 See registration assignment, register 32, bit 12 ... 15
Bit 8 ... 11: Sensor type channel 3
0 ... 15 See registration assignment, register 32, bit 12 ... 15
Bit 12 ... 15: Sensor type channel 4
0 ... 15 See registration assignment, register 32, bit 12 ... 15
Register
32 (proportionate) EEPROM
Register
32 (proportionate) EEPROM
Commissioning
Memory
Access
R/W
Memory
Access
R/W
89
Default settings
0x0000
Default settings
0x0000