WAGO -I/O-SYSTEM 750 Manual page 87

2/4 ai rtd configurable 2-/4-channel analog input module for rtds
Hide thumbs Also See for WAGO-I/O-SYSTEM 750:
Table of Contents

Advertisement

WAGO-I/O-SYSTEM 750
750-464 2/4 AI RTD configurable
Table 71: Communication Control Parameters
Parameter
TIMEOUT
BUF_OVF
PRM_ERR
PRM_UPD
SR_LEN_UPD FALSE
RES
Value range
Meaning
FALSE
The transmission of the parameters has been
completed within the stipulated time (parameter
address 0).
TRUE
The maximum time for the transmission of the
parameters between I/O module and application
was exceeded.
FALSE
Access to the write or read buffer of the I/O
module was permitted.
TRUE
Parameters outside of the write or read buffer
were accessed.
FALSE
The parameter/all parameters previously
transmitted are valid.
TRUE
At least one transmitted parameter was
defective. The flag can either be set after each
parameter that is received or after the
transmission of the parameters is completed.
FALSE
No change in module´s individual parameter
data set.
TRUE
Module's individual parameter data set has been
changed. A respective iPar-Server request is to
be initiated by the PROFIBUS/PROFINET
coupler/controller.
No change in module´s local bus shift register
size.
TRUE
Module´s local bus shift register size will be
changed. The initiation of a local bus reset
sequence is necessary.
FALSE
Reserved for expansions
Commissioning
87
Manual
Version 1.1.0

Advertisement

Table of Contents
loading

This manual is also suitable for:

750-464

Table of Contents