Commissioning
7.1.3.2

Channel Settings

Figure 18: Parameter „Channel"
In the menus Channel 1 ... 4 you can make channel granular settings:
Table 33: Parameter „Channel"
Selection Field
Signal type
Input filter
Channel Diagnosis
Diagnosis: Overload
Diagnosis: Wire break
Manual
Version 1.0.0
Possible Settings
The measurement range can be set and the channel
switched on or off here.
Channel
The channel is switched off. 0x7FFF is
deactivated
delivered as process value.
0 ... 10 V
± 10 V
± 200 mV
0 ... 20 mA
4 ... 20 mA*
3,6 ... 21,0 mA (Namur NE 43)
± 20 mA
Whether the input filter frequency set for this channel in
the "General" menu should be suppressed can be set
with this parameter.
Off*
Input filter is OFF.
On
Input filter is ON.
The diagnostics for one channel can be switched on or
off here.
Off
Channel diagnostics is OFF.
On*
Channel diagnostics is ON.
The overload diagnostics can be switched on or off
here.
On
Overload diagnostics is OFF.
Off*
Overload diagnostics is ON.
The wire break diagnostics for one channel can be
switched on or off here.
On
Wire break diagnostics is ON.
WAGO-I/O-SYSTEM 750
750-471 4AI U/I Diff Galv