WAGO-I/O-SYSTEM 750
750-464 2/4 AI RTD configurable
4.4.7
Ni120 (Minco)
With the setting "Ni120 (Minco)" and activated Siemens format, the I/O module
converts the resistance measured values of Ni120 sensors (Minco) and outputs
them as temperature values.
The temperature values are displayed at a resolution of 1 digit per 0.5 °C.
The status information is depicted in bit 0 ... bit 2 and the digitalized measured
value in bit 3 ... bit 15.
Table 41: Process image for 750-464, Ni120 setting (Minco)
Temperature
°C
---
Short circuit
< −80.0
Underrange
−80.0
−50.0
0.0
50.0
100.0
150.0
200.0
250.0
260.0
> 260.0
Overrange
---
Wire break
1) Temperature values below 0 °C are represented in two's complement binary.
2) When short circuit and wire break monitoring is ON (see section "Behavior in the Event of an
Error")
3) When underrange / overrange limit is ON (see section "Behavior in the Event of an Error")
4) Status information: X: Not used, F: Short circuit, wire break, Ü: Overrange
Numeric value
Resistance
Ω
Binary
< 9.00
'1111.1011.0000.0 011'
2)
66.60
'1111.1011.0000.0 001'
3)
66.60
'1111.1011.0000.0 000'
86.16
'1111.1100.1110.0 100'
120.00
'0000.0000.0000.0 000'
157.75
'0000.0011.0010.0 000'
200.64
'0000.0110.0100.0 000'
248.95
'0000.1001.0110.0 000'
303.45
'0000.1100.1000.0 000'
366.53
'0000.1111.1010.0
380.31
'0001.0000.0100.0 000'
>380.31
'0001.0000.0100.0 001'
3)
> 5500.00
'0001.0000.0100.0 011'
2)
Process Image
1)
with status information
XFÜ
Hex.
Dec.
0xFB03
−1277
0xFB01
−1279
0xFB00
−1280
0xFCE0
−800
0x0000
0x0320
800
0x0640
1600
0x0960
2400
0x0C80
3200
000'
0x0FA0
4000
0x1040
4160
0x1041
4161
0x1043
4163
57
Status
LED
4)
byte
error
hex.
AI 1, 2
0x51
on
0x41
on
0x00
off
0x00
off
0
0x00
off
0x00
off
0x00
off
0x00
off
0x00
off
0x00
off
0x00
off
0x42
on
0x62
on
Manual
Version 1.1.0