Pt1000 (Acc. Iec 751); Table 28: Process Image For 750-464, Pt1000 Setting (Acc. Iec 751) - WAGO -I/O-SYSTEM 750 Manual

2/4 ai rtd configurable 2-/4-channel analog input module for rtds
Hide thumbs Also See for WAGO-I/O-SYSTEM 750:
Table of Contents

Advertisement

44
Process Image
4.3.4

Pt1000 (acc. IEC 751)

With the setting "Pt1000 (acc. IEC 751)", the I/O module converts the resistance
measured values of Pt1000 sensors (acc. IEC 751) and outputs them as
temperature values.
The temperature values are displayed at a resolution of 1 digit per 0.1 °C in one
word (16-bit). Temperature values below 0 °C are represented in two's
complement binary. As a result, 0 °C corresponds to the numeric value 0x0000
and 100 °C to the numeric value 0x03E8 (dec. 1000).
The possible numeric range corresponds to the defined temperature range of
−200 °C ... +850 °C for Pt1000 sensors (acc. IEC 751).

Table 28: Process image for 750-464, Pt1000 setting (acc. IEC 751)

Temperature
°C
---
Short circuit
< −200.0
Underrange
−200.0
−100.0
0.0
100.0
200.0
500.0
750.0
800.0
850.0
> 850.0
Overrange
---
Wire break
1) Temperature values below 0 °C are represented in two's complement binary.
2) When short circuit and wire break monitoring is ON (see section "Behavior in the Event of an
Error")
3) When underrange / overrange limit is ON (see section "Behavior in the Event of an Error")
Manual
Version 1.1.0
Resistance
Ω
Binary
< 9.00
'1111.1000.0011.0000'
2)
< 185.20
'1111.1000.0011.0000'
3)
185.20
'1111.1000.0011.0000'
602.56
'1111.1100.0001.1000'
1000.00
'0000.0000.0000.0000'
1385.06
'0000.0011.1110.1000'
1758.56
'0000.0111.1101.0000'
2809.78
'0001.0011.1000.1000'
3606.38
'0001.1101.0100.1100'
3757.04
'0001.1111.0100.0000'
3904.81
'0010.0001.0011.0100'
> 3904.81
'0010.0001.0011.0100'
3)
> 5500.00
'0010.0001.0011.0100'
2)
WAGO-I/O-SYSTEM 750
750-464 2/4 AI RTD configurable
1)
Numeric value
Hex.
0xF830
0xF830
0xF830
0xFC18
0x0000
0x03E8
0x07D0
0x1388
0x1D4C
0x1F40
0x2134
0x2134
0x2134
Status
LED
byte
error
hex.
AI 1, 2
Dec.
−2000
0x51
on
−2000
0x41
on
−2000
0x00
off
−1000
0x00
off
0
0x00
off
1000
0x00
off
2000
0x00
off
5000
0x00
off
7500
0x00
off
8000
0x00
off
8500
0x00
off
8500
0x42
on
8500
0x62
on

Advertisement

Table of Contents
loading

This manual is also suitable for:

750-464

Table of Contents