Ni100 (Acc. Din 43760); Table 40: Process Image For 750-464, Ni100 Setting (Acc. Din 43760) - WAGO -I/O-SYSTEM 750 Manual

2/4 ai rtd configurable 2-/4-channel analog input module for rtds
Hide thumbs Also See for WAGO-I/O-SYSTEM 750:
Table of Contents

Advertisement

56
Process Image
4.4.6

Ni100 (acc. DIN 43760)

With the setting "Ni100 (acc. DIN 43760)" and activated Siemens format, the I/O
module converts the resistance measured values of Ni100 sensors (acc.
DIN 43760) and outputs them as temperature values.
The temperature values are displayed at a resolution of 1 digit per 0.5 °C.
The status information is depicted in bit 0 ... bit 2 and the digitalized measured
value in bit 3 ... bit 15.

Table 40: Process image for 750-464, Ni100 setting (acc. DIN 43760)

Temperature
°C
---
Short circuit
< −60.0
Underrange
−60.0
−50.0
0.0
50.0
100.0
150.0
200.0
250.0
300.0
>300.0
Overrange
---
Wire break
1) Temperature values below 0 °C are represented in two's complement binary.
2) When short circuit and wire break monitoring is ON (see section "Behavior in the Event of an
Error")
3) When underrange / overrange limit is ON (see section "Behavior in the Event of an Error")
4) Status information: X: Not used, F: Short circuit, wire break, Ü: Overrange
Manual
Version 1.1.0
Numeric value
Resistance
Ω
Binary
< 9.00
'1111.1100.0100.0 011'
2)
< 69.52
'1111.1100.0100.0 001'
3)
69.52
'1111.1100.0100.0 000'
74.26
'1111.1100.1110.0 000'
100.00
'0000.0000.0000.0 000'
129.11
'0000.0011.0010.0 000'
161.78
'0000.0110.0100.0 000'
198.64
'0000.1001.0110.0 000'
240.66
'0000.1100.1000.0 000'
289.16
'0000.1111.1010.0 000'
345.66
'0001.0010.1100.0 000'
> 345.66
'0001.0010.1100.0 001'
3)
> 5500.00
'0001.0010.1100.0 011'
2)
WAGO-I/O-SYSTEM 750
750-464 2/4 AI RTD configurable
1)
with status information
XFÜ
Hex.
Dec.
0xFC43
−957
0xFC41
−959
0xFC40
−960
0xFCE0
−800
0x0000
0x0320
800
0x0640
1600
0x0960
2400
0x0C80
3200
0x0FA0
4000
0x12C0
4800
0x12C1
4801
0x12C3
4803
Status
LED
4)
byte
error
hex.
AI 1, 2
0x51
on
0x41
on
0x00
off
0x00
off
0
0x00
off
0x00
off
0x00
off
0x00
off
0x00
off
0x00
off
0x00
off
0x42
on
0x62
on

Advertisement