Calibration; Figure 19: Calibration Dialog - WAGO -I/O-SYSTEM 750 Manual

2/4 ai rtd configurable 2-/4-channel analog input module for rtds
Hide thumbs Also See for WAGO-I/O-SYSTEM 750:
Table of Contents

Advertisement

WAGO-I/O-SYSTEM 750
750-464 2/4 AI RTD configurable
2/4 Analogeingangsklemme Analog 750-464 (Skalierung)
7.3.3.3

Calibration

Calibration in "4-channel mode" only!
The module can only be calibrated depending on the topology in "4-channel
mode"!

Figure 19: Calibration Dialog

To select the respective channel, select the [Channel 1] ... [Channel 4] radio
button.
To enter the value in hexadecimal format, select the [hexadecimal] radio button.
To enter the value in decimal format, select the [decimal] radio button.
To select the Offset and Gain factory setting, select the [Manufacturer
Calibration] radio button.
To enter your settings in the Offset and Gain fields, select the [User
Calibration] radio button.
The corresponding value appears in the A/D raw value field.
The value appears in °C in the Process value field.
The measuring circuits can be calibrated independently in the same way.
Commissioning 101