Ni100 (Acc. Din 43760); Table 29: Process Image For 750-464, Ni100 Setting (Acc. Din 43760) - WAGO -I/O-SYSTEM 750 Manual

2/4 ai rtd configurable 2-/4-channel analog input module for rtds
Hide thumbs Also See for WAGO-I/O-SYSTEM 750:
Table of Contents

Advertisement

WAGO-I/O-SYSTEM 750
750-464 2/4 AI RTD configurable
4.3.5

Ni100 (acc. DIN 43760)

With the setting "Ni100 (acc. DIN 43760)", the I/O module converts the resistance
measured values of Ni100 sensors (acc. DIN 43760) and outputs them as
temperature values.
The temperature values are displayed at a resolution of 1 digit per 0.1 °C in one
word (16-bit). Temperature values below 0 °C are represented in two's
complement binary. As a result, 0 °C corresponds to the numeric value 0x0000
and 100 °C to the numeric value 0x03E8 (dec. 1000).
The possible numeric range corresponds to the defined temperature range of
−60 °C ... +300 °C for Ni100 sensors (acc. DIN 43760).

Table 29: Process image for 750-464, Ni100 setting (acc. DIN 43760)

Temperature
°C
---
Short circuit
< −60.0
Underrange
−60.0
−50.0
0.0
50.0
100.0
150.0
200.0
250.0
300.0
> 300.0
Overrange
---
Wire break
1) Temperature values below 0 °C are represented in two's complement binary.
2) When short circuit and wire break monitoring is ON (see section "Behavior in the Event of an
Error")
3) When underrange / overrange limit is ON (see section "Behavior in the Event of an Error")
Resistance
Ω
Binary
< 9.00
'1111.1101.1010.1000'
2)
< 69.52
'1111.1101.1010.1000'
3)
69.52
'1111.1101.1010.1000'
74.26
'1111.1110.0000.1100'
100.00
'0000.0000.0000.0000'
129.11
'0000.0001.1111.0100'
161.78
'0000.0011.1110.1000'
198.64
'0000.0101.1101.1100'
240.66
'0000.0111.1101.0000'
289.16
'0000.1001.1100.0100'
345.66
'0000.1011.1011.1000'
> 345.66
'0000.1011.1011.1000'
3)
> 5500.00
'0000.1011.1011.1000'
2)
1)
Numeric value
Hex.
0xFDA8
0xFDA8
0xFDA8
0xFE0C
0x0000
0x01F4
0x03E8
0x05DC
0x07D0
0x09C4
0x0BB8
0x0BB8
0x0BB8
Process Image
45
Status
LED
byte
error
hex.
AI 1, 2
Dec.
−600
0x51
on
−600
0x41
on
−600
0x00
off
−500
0x00
off
0
0x00
off
500
0x00
off
1000
0x00
off
1500
0x00
off
2000
0x00
off
2500
0x00
off
3000
0x00
off
3000
0x42
on
3000
0x62
on
Manual
Version 1.1.0

Advertisement

Table of Contents
loading

This manual is also suitable for:

750-464

Table of Contents