Metallic Roof Parapet - OBO Bettermann isCon System Instructions

Lightning protection
Table of Contents

Advertisement

2
Rd 8
Note!
System instructions OBO isCon
x
7
3
Fig 66: isCon
7 2

Metallic roof parapet

If there is a metallic roof parapet
ponent of the lightning protection system, the isCon
connected to it using a suitable OBO connection component
The potential is connected to the protective equipotential bonding on the
air-termination rod via the potential connection clip
Alternatively, the potential can be connected at the air-termination rod
stand
, provided that the potential connection clip
4
ing the electrical connection between the black, weakly conductive layer
or the protective jacket of the isCon
rod.
The distance x (= separation distance s multiplied by two) between the
potential connection terminal
should be noted.
The conductor type isCon BA 45 SW (Basic) can be routed with or with-
out potential connection. If the conductor is routed without a
potential connection, observe "Mounting variant 2 for isCon BA 45 SW"
on page 54.
lightning protection
®
1
6
5
conductor connected to stand-off ring conductor
®
which is used as a natural com-
1
conductor and the air-termination
®
and the rear connection element
5
Mounting variants
4
conductor can be
®
2
(type 927 2 6-K).
3
is mounted, creat-
3
.
6
EN | 59