Including The Air-Termination Rod Stand In The Functional Equipotential Bonding; Installing Additional Potential Connections - OBO Bettermann isCon System Instructions

Lightning protection
Table of Contents

Advertisement

System instructions OBO isCon
6 6 3
Including the air-termination rod stand in the functional
equipotential bonding
Fasten the crossbar (included in scope of delivery) to the air-termi-
nation rod and connect a round conductor Rd 8-10 to the equipotential
bonding of the building.
Fig 61: Connection of the equipotential bonding to the insulated air-termination
rod stand
6 6 4

Installing additional potential connections

If the isCon
®
parallel to them, then we recommend additional measures to improve the
equipotential bonding.
To do this, connect the isCon
lations, e.g. cable racks, pipelines or parapet plates, after the first poten-
tial connection using the potential connection element.
Fig 62: Creating additional equipotential bonding
lightning protection
®
Assembling the air-termination rod
conductor crosses earthed, metallic installations, or is run in
conductor multiple times with these instal-
®
Rd 8-10
EN | 55