Product description
Type
Colour
Equivalent separation distance,
air (cm)
Equivalent separation distance,
solid materials (cm)
Equivalent separation distance,
mixed materials
External diameter
Round conductor, multi-wire, Cu
Cable weight
Temperature range for routing
Operating temperature
Bend radius
Maximum tensile load
Routing in the earth
Can be painted
Protection against touch
voltages
Weathering resistance (UV-
stabilised)
Fire load (kWh/m)
Fire behaviour
Self-extinguishing
Lightning current carrying
capacity (class/Iimp (kA)
Testing certificate according to
IEC TS 62561-8
Halogen-free
Softener
10 | EN
5 Protective jacket
6 External jacket, grey
The isCon
conductor may only be connected to air-termination rods or
®
forwarding systems using system-tested OBO connection elements (see
also "5.2 Mounting the connection elements isCon connect, isCon con 2
and isCon con PRE" on page 30).
isCon BA 45
isCon Pro 75
SW
SW
Black
Black
≤ 45
≤ 75
≤ 90
≤ 150
~ 20 mm
~ 20 mm
~ 0.570 kg/m
~ 0.570 kg/m
min. 200 mm
min. 200 mm
No
No
No
No
No
No
Ozone resistant according to DIN EN 60811-2-1 Section 8
Sunlight Resistance Test according to UL 1581 Section 1200
Coldness impact resistance according to-DIN EN 60811-1-4 Section 8.5
3.3
n/a
n/a
H1/150
H1/150
Tab 2: Technical data of the isCon
isCon Pro+ 75
isCon Pro+ 75
SW
GR
Black
Grey
≤ 75
≤ 75
≤ 150
≤ 150
See EN 62305-3
~ 23 mm
~ 26 mm
35 mm
2
~ 0.694 kg/m
~ 0.868 kg/m
min. –5 °C, max. 40 °C
min. –30 °C, max. 70 °C
min. 230 mm
min. 260 mm
1, 750 N
No
Yes
No
Yes
(does not apply
when used as
protection
against touch
voltages)
No
Yes
4.3
5.1
Yes
Yes
H1/150
Yes
Yes
None
conductors
®
isCon PR 90
SW
Black
≤ 90
≤ 180
~ 23 mm
~ 0.666 kg/m
min. 230 mm
No
No
No
4.2
n/a
H2/200
OBO Bettermann