Fastening the isCon
For one isCon
Mount the connection plate (type isCon AP1-16 VA) at the bottom
end of the air-termination rod, as shown in Fig. 41. Tightening torque:
24 Nm
Mount the connection element of the isCon
tion plate. Tightening torque: 24 Nm.
Fig 41: Mounting the connection plate for one isCon
mination rod
For multiple isCon
For 2 isCon conductors, use the connection plate for 2 conductor
(type isCon AP2-16 VA). When connecting 4 conductors, mount 2
connection plates over each other (see Fig. 42).
Mount the connection element of the isCon
nection plate. Tightening torque: 24 Nm.
Run the conductors downwards on the air-termination rod, ideally op-
posite one another (see Fig. 42).
Install the conductors as far apart from each other as possible, if the
installation conditions permit this.
24 Nm
Fig 42: Fastening multiple isCon
lightning protection
®
Assembling the air-termination rod
conductor on the air-termination rod
®
conductor:
®
conductors
®
conductors on the mast
®
conductor on the connec-
®
24 Nm
®
conductor on the air-ter-
conductor on the con-
®