OBO Bettermann isCon System Instructions page 64

Lightning protection
Table of Contents

Advertisement

Mounting variants
64 | EN
Installation of the protection against touch voltages
Always route the isCon
remove any soiling on the conductor.
In the area to be protected, route the isCon
1
a length of at least 2.5 m plus the separation distance (s). This corre-
sponds to a length of approx. 3–5 m.
Note!
W ith an increasing length of the isCon
tact voltage occurring in the earth also increases.
Remove the grey external jacket 0.5 m below the connector (see
2
"5.1.1 Removing the grey external jacket (isCon Pro+ 75 GR)" on
page 28) and fasten the first conductor bracket (type isCon H VA)
directly to solid masonry.
If a direct connection to solid masonry is not possible, a separate
potential connection must be made using an earthed rain gutter or
parapet.
3
Attach all further conductor brackets (type isCon H 26 VA) at a dis-
tance of ≤ 1 m.
4
Maintain the minimum bend radius of 260 mm.
Fig 71: Installation of the isCon
touch voltages
conductor Pro+ 75 GR so that it is vertical and
®
5311 519
2
1
conductor Pro+ 75 GR as protection against
®
conductor Pro+ 75 GR to
®
conductor Pro+ 75 GR, the con-
®
5408 056
3
2146 207
r 260 mm
4