Installing The Iscon ® System; Cutting And Stripping The Iscon Conductor; Removing The Grey External Jacket (Iscon Pro+ 75 Gr) - OBO Bettermann isCon System Instructions

Lightning protection
Table of Contents

Advertisement

Installing the isCon® system
WARNING
ATTENTION
28 | EN
5
Installing the isCon
Risk of electric shock!
If there is a lightning strike in the lightning protection system, lethal voltag-
es can occur in the system.
Do not work on the lightning protection system during a thunderstorm or
if there is the risk of one, and do not install air-termination masts in the
immediate vicinity of high-voltage cables.
5 1
Cutting and stripping the isCon
The isCon® conductor is sold by the metre and in five variants:
Conductor type
isCon PR 90 SW
isCon Pro 75 SW
isCon Pro+ 75 SW
isCon Pro+ 75 GR
isCon BA 45 SW
Tab 10: Product variants of the isCon
The grey isCon
be used for protection against touch voltages up to a length of max. 5 m.
If the conductor is not used as protection against touch voltages, then
coloured painting, e.g. with facade paint, is also possible. As the external
grey jacket is non-conductive, it must be removed in the contact areas.
Shorten the isCon
standard cable cutters or saw.
5 1 1

Removing the grey external jacket (isCon Pro+ 75 GR)

In the case of the isCon Pro+ 75 GR conductor, before attaching ele-
ments for potential connection, remove the grey external jacket in the
contact area, so that the connection comes into contact with the protec-
tive jacket.
Risk of damage!
The black, weakly conductive layer may not be removed, as otherwise
the connection to the building's equipotential bonding can be interrupted.
Observe the cutting depth of the grey external jacket of 1.5 mm.
When mounting the isCon
Remove 50 mm of the grey external jacket with a cable knife.
Fig 17: Cutting and removing the grey outer jacket in the contact area
system
®
Article no.
5408 018
5408 008
5408 002, 5408 004, 5408 006
5407 995, 5407 997
5408 014
conductor
®
conductor is also suitable for routing in the earth and can
®
conductor on-site to the required length using
®
connection elements:
®
5 0
m m
conductor
®
1.5 mm
> 1.5 mm