Assembling the air-termination rod
ATTENTION
40 | EN
Preparing the isCon
conductor
®
When using the isCon Pro+ 75 LGR:
Using a cable knife, remove the grey external jacket to a length of
50 mm (see also "5.1 Cutting and stripping the isCon
page 28).
Mount the connection element (Fig. 39 No.
ductor as described in sections "5.1.2 Revealing the copper core for
connection" on page 29 and "5.2 Mounting the connection elements
isCon connect, isCon con 2 and isCon con PRE" on page 30.
Only for the grey conductor isCon Pro+ 75 GR:
To connect the potential connection element, the grey external jacket in
the contact area must be removed.
Risk of damage!
The black, weakly conductive layer may not be removed, as otherwise the
connection to the building's equipotential bonding can be interrupted. In
the case of the grey external jacket, maintain a maximum cutting depth of
1.5 mm.
Measure 1,500 mm from the bottom edge of the isCon
element.
Remove 50 mm of the grey external jacket with a cable knife.
1,500 mm
Fig 40: Removing the grey external jacket
) on the isCon
3
m
5 0 m
m
5 0 m
conductor" on
®
con-
®
connection
®
1.5 mm
> 1.5 mm