OBO Bettermann isCon System Instructions page 54

Lightning protection
Table of Contents

Advertisement

Assembling the air-termination rod
54 | EN
Fig 58: Distance between the connection element and the potential connection
terminal
With metallic, earthed substrates, use the metallic conductor bracket.
When screwed directly to the substrate, it also provides equipotential
bonding.
Note!
W hen using the grey isCon
be removed in the area of the conductor bracket (see "5.1.1 Removing the
grey external jacket (isCon Pro+ 75 GR)" on page 28).
Fig 59: Equipotential bonding using isCon H VA conductor bracket on metallic
substrate, grey external jacket removed in contact area.
Mounting variant 2 for isCon BA 45 SW
The conductor type isCon BA 45 SW can also be routed without a po-
tential connection. When mounted without a potential connection, the
minimum distance (x) must be complied with in both directions, starting
from the last insulated spacer. There may be no electrically conductive
parts within the perimeter of the calculated separation distance (s) (see
Fig. 60).
Fig 60: Mounting variant for the isCon BA 45 SW conductor without potential
connection
x
conductor, the light grey external jacket must
®
x
s
≥ 6 mm²
OBO Bettermann