Fastening The Air-Termination Rod To Pipes, A Wall Or T Support - OBO Bettermann isCon System Instructions

Lightning protection
Table of Contents

Advertisement

Assembling the air-termination rod
48 | EN
6 4
Fastening the air-termination rod to pipes, a wall or
T support
The isCon
supports for mounting isFang air-termination rods with air-termination rod
stands (see "3.4.2 Air-termination rod support for isFang mounting" on
page 17). This applies to air-termination rods with openings at the side
or the bottom, as well as to rods with an external isCon
Fig 53: Fastening air-termination rods to pipes, walls or T supports
Please note:
– Fasten the air-termination rod to the building structure using the sup-
ports listed in Tab. 6 on page 17 and suitable fastening materials.
– In the case of a non-metallic building structure, connect the equipoten-
tial bonding directly to the equipotential bonding of the air-termination
rod (see "6.6 Attaching the potential connection" on page 50).
Note!
I n the case of a metallic, earthed building structure, the equipotential
bonding is created using the metallic fastening clips of the air-termination
rod. No additional connection is required.
system can offer supports for fastening to pipes, walls or T
®
conductor.
®