CAUTION
WARNING
System instructions OBO isCon
When mounting equipotential bonding elements (clips, clamps):
Using a cable knife, remove the grey external jacketing in the contact
area along a length of 100 mm.
Fig 18: Releasing the grey outer jacketing within the cable routing
5 1 2

Revealing the copper core for connection

Risk of injury!
Sharp blades in the cutting head of the stripping tool isCon stripper 2.
Do not reach into the cutting head of the stripping tool isCon stripper 2!
Using the stripping tool isCon stripper 2, adjust the stripping length to
25 mm.
Fig 19: Adjusting the stripping length
Insert the isCon
sure, turn the handle in a clockwise direction until the preset length of
the insulation has been cut off.
Risk of function loss!
If there is a lightning strike, connection faults can lead to devices being
destroyed, fires triggered and human lives being endangered.
After stripping, ensure an even cut edge.
Remove excesses by hand.
lightning protection
®
Installing the isCon® system
m
1 0 0 m
25 mm
conductor into the cutting head and, with slight pres-
®
1.5 mm
> 1.5 mm