Checking The Lightning Protection System - OBO Bettermann isCon System Instructions

Lightning protection
Table of Contents

Advertisement

System instructions OBO isCon
8

Checking the lightning protection system

The entire lightning protection system must be tested according to DIN
EN 62305-3 (IEC 62305-3) and DIN EN 62305-3, Supplementary Sheet
5.
Protection
class
I and II
III and IV
Critical situations include structures containing sensitive systems, or
1)
office and commercial buildings or places in which a large number of
people meet.
Note!
I n the case of lightning protection systems in structures at risk of explo-
sion, we recommend carrying out a visual inspection every 6 months.
Carrying out a visual inspection
Check that the black, weakly conductive layer of the isCon
is undamaged. An interruption of this layer will prevent the conductor
from functioning. In this case, replace the isCon
When using the isCon
touch voltages, check that the grey external jacket is undamaged.
Damage to this layer will prevent the conductor from functioning. In
this case, replace the isCon
Check that the protective jacket of the isCon
continuously present and has a material thickness of at least 0.2 mm.
In this case, replace the isCon
jacket may be interrupted and damaged. The protective jacket may be
damaged but must be continuously present.
Check that the potential connection cables and all connection compo-
nents, in particular the potential connection elements, are undamaged.
There must be a low-resistance connection between all the elements.
If necessary, restore the flow.
Check that the function of the holders and other mounting elements is
not impaired. If necessary, retighten the screws.
Check that only products of the isCon
elements, are used during mounting. Replace the parts which are not
components of the isCon
system.
When using the isCon
touch voltages, check whether it is soiled. If this is the case, remove it.
lightning protection
®
Checking the lightning protection system
Visual inspection
Comprehensive test
Annually
Every 2 years
Every 2 years
Every 4 years
Pro+ 75 GR conductors as protection against
®
Pro+ 75 GR conductors.
®
Pro+ conductor. The grey external
®
system with appropriate products of the
®
Pro+ 75 GR conductor as protection against
®
Comprehensive test
in critical situations
Annually
Annually
conductor
®
conductor.
®
Pro+ conductors is
®
system, such as connection
®
1)
EN | 65