Installation In Potentially Explosive Areas - OBO Bettermann isCon System Instructions

Lightning protection
Table of Contents

Advertisement

System instructions OBO isCon
4 4

Installation in potentially explosive areas

The isCon Pro+ conductor is ignition-free and can thus be used in light-
ning protection systems, which are to be located in potentially explosive
areas. Here, the isCon
Ex zone 1/2 and 21/22.
If necessary, an appropriate DEKRA test report can be obtained from
your OBO contact.
Note!
T he system operator must divide a structure into Ex zones (see IEC
60079-10-1 and 2).
When planning and running a lightning protection system through Ex
zones, the following rules must particularly be taken into account:
DIN EN 62305-3 – Appendix D – "Additional information for lightning
protection systems for structures in areas with the risk of explosion"
VDE 0185-305-3 – Supplementary sheet 2 – "Additional information for
special structures"
According to this, planners, craftspeople and testers of lightning protec-
tion systems must meet the following requirements and levels of know-
ledge in potentially explosive areas:
General principles of explosion protection
General principles of protection ratings and device labelling
Technical rules for hazardous substances (TRGS 800,751)
Technical rules for operational safety (TRBS 2152)
Testing, maintenance and repair requirements and knowledge of the
appropriate technologies and devices
Meaning of work permission systems and safe electrical separation in
potentially explosive areas of explosion protection
For Ex systems with Ex zone 2 and 22, Supplementary sheet 2 (VDE
0185-305-3, Point 4.3) states that a potentially explosive atmosphere will
only occur in rare, unforeseen circumstances. Therefore, it is possible to
position air-termination units in Ex zones 2 and 22, taking Appendix D in
DIN EN 62305-3 (VDE 0185-305-3) into account.
In the case of installations in potentially explosive areas, you must
connect the isCon
equipotential bonding at regular intervals. See "6.6.5 Creating additional
equipotential bonding for isCon Pro+ in potentially explosive areas" on
page 56 for more information.
lightning protection
®
Pro+ conductor may be run through the areas of
®
Pro+ conductor beyond the potential connection to the
®
Planning an installation
EN | 25