7 1 3
CAUTION
Mounting instructions isCon
Cutting and removing the grey outer jacket in the contact area
Fig 18:
1. To mount the connection elements, at the ends of the isCon
ductor, remove 50 mm of the grey external jacket with a cable knife.
Maximum cutting depth: 1.5 mm.
Fig 19:
Releasing the grey outer jacketing within the cable routing
2. Using a cable knife, remove the grey external jacketing in the contact
area of equipotential bonding elements along a length of 100 mm.
Revealing the copper core for connection
Risk of injury!
Sharp blades in the cutting head of the stripping tool isCon stripper 2.
Do not reach into the cutting head of the stripping tool isCon stripper 2!
lightning protection system
®
Installing the isCon® system
5 0
m m
m
1 0 0 m
1,5 mm
> 1,5 mm
con-
®
1,5 mm
> 1,5 mm
31 | DE