Installing The Iscon ® System; Preparing The Iscon ® Conductor; Shortening The Iscon ® Conductor; Stripping The Grey External Jacket (Iscon Pro+ 75 Gr) - OBO Bettermann isCon PR 90 SW Mounting Instructions

Lightning protection system
Hide thumbs Also See for isCon PR 90 SW:
Table of Contents

Advertisement

Installing the isCon® system
7
WARNING
7 1
7 1 1
7 1 2
ATTENTION
30 | DE
Installing the isCon
Risk of electric shock!
If there is a lightning strike in the lightning protection system, lethal voltages
can occur in the system. Do not work on the lightning protection system during
a thunderstorm or if there is the risk of one, and do not install air-termination
masts in the immediate vicinity of high-voltage cables.
The isCon
system is installed in the following steps:
®
– Preparation of the isCon
elements and equipotential bonding
– Mounting of the connection elements
– Assembly of the air-termination rods and connection of the isCon
conductors
– Connection to the equipotential bonding
Preparing the isCon
The isCon
conductor is sold by the metre and in five variants:
®
Conductor type
isCon PR 90 SW
isCon Pro 75 SW
isCon Pro+ 75 SW
isCon Pro+ 75 GR
isCon BA 45 SW
Tab 9: Product variants of the isCon
Shortening the isCon
1. Determine the required conductor length, as described in "6.3 Con-
ductor lengths and lightning protection classes" on page 25.
2. Shorten the isCon
®
standard cable cutters or saw.

Stripping the grey external jacket (isCon Pro+ 75 GR)

In the case of the isCon Pro+ 75 GR conductor, before attaching con-
nection elements and elements for potential connection, remove the grey
external jacket in the contact area, so that the connection comes into
contact with the protective jacket.
Risk of damage!
The black, weakly conductive layer may not be removed, as otherwise the con-
nection to the building's equipotential bonding can be interrupted. In the case of
the grey external jacket, maintain a maximum cutting depth of 1.5 mm.
system
®
conductor for the mounting of connection
®
conductor
®
Article number
5408018
5408008
5408002, 5408004, 5408006
5407995, 5407997
5408014
®
conductor
conductor
®
conductor on-site to the required length using
®
OBO Bettermann