DR300 Operation and Technical Manual
4.5.

Fuse Information

The Soft-Start / Voltage Select Board contains four fuses (F1-4) used in the Voltage
Select circuit to protect the transformers. Fuses F1 and F3 (Typical value: 4 Amps)
provide the primary protection for 100 and 115 VAC operation. Fuses F2 and F4 (Typical
value: 3 Amps) provide the primary protection for 200 and 230 VAC operation. Fuses F1
and F2 are used to protect the transformer connected to J3. Fuses F3 and F4 are used to
protect the transformer connected to J5. Fuses are shown in Figure 4-1. Table 4-6 lists the
Part #'s for these fuses.
Table 4-6.
Fuse Replacement Part Numbers
FUSE
3 amp, 3AG
4 amp, 3AG
Disconnect Mains power before opening chassis. Fuses must not be changed with
Mains power applied to unit.
Refer to Chapter 5, section 5.4., for Fuse Replacement information regarding the
DR300.
Version 1.5
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Manufacturer P/N
PN. BK/MDA-3
PN. BK/MDA-4
∇ ∇ ∇
Aerotech, Inc.
Aerotech P/N
EIF103
EIF104
Soft-Start
4-5