Soft-Start
4.2.
Soft-start operation is an automatic function that limits inrush current to approximately 10
amps for 100/115 VAC operation and 20 amps for 200/230 VAC operation. Inrush
current limiting is only activated during initial power-up or when AC power interruptions
last longer than .3 seconds. Short Power interruptions (less than about .3 seconds) will not
initiate a soft-start activation. This prevents the possibility of soft-start induced nuisance
trips during normal operation.
WARNING
4-2
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
DR300 Operation and Technical Manual

Soft-Start Operation

The Soft-Start circuit requires +24 VDC for proper operation (provided internally).
Damage to the Soft-Start circuit may result if +24 VDC is not connected.
Aerotech, Inc.
Version 1.5