Starting The Generator From The Remote; Me-Ags-N Operation/Monitoring; Controlling The Ags - Magnum Energy ME-ARC Series Owner's Manual

Advanced remote control
Hide thumbs Also See for ME-ARC Series:
Table of Contents

Advertisement

7.2.1.2 Starting the Generator from the Remote

To confi rm that the generator will turn on and run from the remote, fi rst ensure
the AGS status is Off or Ready (see Section 7.2.1.1). Then:
1.
Press the CTRL button, and then rotate the SELECT knob to the 03 Gen
Control menu.
2.
Press the SELECT knob, and then rotate it to the ON setting.
3.
Press the SELECT knob to activate the generator test.
Once the generator starts, it should run until you change the 03 Gen Control
menu to OFF (before turning off). After two minutes, view the STATUS LED
and ensure it turns solid green (a solid green STATUS LED means the gen-
erator has started successfully and is providing the gen run sense signal to
the AGS module).
Note: If the generator attempted to start but did not run, continue to wait,
the AGS will attempt to start the generator three more times.
If your AGS/generator system started (may attempt autostart x4), ran, and
the STATUS LED came on and stayed on (not blinking), then the wiring from
the AGS to the generator is correct. You are now ready to enable the AGS by
setting the 03 Gen Control setting in your remote to AUTO (see Section 7.3.1).
Info: The AGS attempts to start the generator four times. If after
four attempts the generator fails to start, the STATUS LED turns
red—indicating a fault.
If a generator fault displays or the AGS module's STATUS LED shows a fault
condition (solid red LED indication), refer to Section 7.8 for assistance.

7.3 ME-AGS-N Operation/Monitoring

This section provides the menus under the ME-ARC's CTRL, METER, and TECH
buttons that determine how to control and operate the generator. The section
also includes menus that are used to help monitor the AGS and the genera-
tor's starting and running conditions.

7.3.1 Controlling the AGS

The AGS uses the CTRL: 03 Gen Control menu to activate the generator either
manually or automatically. Press the CTRL button on the ME-ARC remote and
rotate the SELECT knob to the 03 Gen Control menu.
CTRL: 03 Gen Control
This menu is used to manually turn the connected generator on and off, or
to select the AUTO feature which enables the active generator autostart and
autostop settings to control the connected generator. Available options are:
OFF: The OFF selection turns the generator off if it is running from either a
manual "on" command or an autostart command. When OFF is selected, the
AGS is prevented from starting the generator automatically (default).
Info: When OFF is selected, the AGS turns off immediately without
any cooldown time (if set).
Info: If DC power is lost to the remote or to the inverter system,
this menu resets to the default OFF position for safety.
Info: If the generator is manually started from the generator con-
trol panel or a generator remote panel, selecting OFF may not shut
down the generator.
© 2012 Magnum Energy, Inc.
7.0 Using an AGS Module
77

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Me-arc50

Table of Contents