Tech: 02 Revisions; Tech: 03 Inv Model; Tech: 04 Fault History - Magnum Energy ME-ARC Series Owner's Manual

Advanced remote control
Hide thumbs Also See for ME-ARC Series:
Table of Contents

Advertisement

TECH: 02 Revisions

Displays the revisions of those devices that are connected to the Magnum
network. Rotate the SELECT knob to scroll through the revisions. The fol-
lowing devices display revisions (if connected to remote): inverter, remote,
AGS-N, BMK, and router.
Info: The BMK, AGS, and the remote accessories may display a
"0.0" revision. Either the accessory is not installed, there is no com-
munication because of a bad or miswired network cable, the device
is not powered, or the device is bad.
If the ME-ARC is connected to a router (ME-RTR), the router revi-
sion will be displayed, but not all functions of the ME-ARC will be
available. The ME-ARC has limited functions as a second remote
connected to the router. Refer to the ME-RTR Router Owner's Manual
(PN: 64-0020) for a complete list of active menus when the ME-ARC
is connected to the router.

TECH: 03 Inv Model

Displays the model number of the connected inverter.
Info: When the 03 Inv Model menu item displays "Unknown", the
remote is unable to determine the inverter model. This happens
when the remote is connected to a later/newer inverter model not
recognized by an older remote. All remote menu selections and fea-
tures that are available in the inverter will function normally.
Info: When an inverter is stacked in parallel or series, there will be
a stacking indication following the model number. The indication will
identify the following stacking conditions: "PM" – Parallel Master; "PS"
– Parallel Slave; "SM" – Series Master; "SS" – Series Slave.
Info: The revision may display "0.0" for several reasons. Either
the device is not installed, there is no communication due to a
bad or miswired network cable, or the device is not powered or is
bad.

TECH: 04 Fault History

These menus display a history of the connected inverter and any networked
AGS, and provide a way to clear all recorded fault history.
Info: All recorded fault history displays will be retained (except
for the day the fault occurred), even if power is removed from the
remote. If no fault history is recorded, the display shows "No Error
Record".
04A Inv Faults – This menu displays a history of the last nine inverter/
charger faults. Information for each fault displays from the most recent
fault (H1) to the earliest/past recorded faults (H2 up to H9). Refer to
Figure 3-8.