6.0 Troubleshooting

6.0 Troubleshooting
The remote may not be functioning correctly, use the following table to
help fi nd a solutions.

Table 6-1, Remote Control Troubleshooting Guide

Symptom
Possible Cause
Display shows
Static electricity
unrecognizable
may have been
letters or
discharged into the
symbols
LCD display.
LCD text
RJ11 connections on
display is
communication cable
locked-up,
are not making a
pushing any
good connection.
button has
no response
- may show
"revision" or
"connecting"
Remote not getting
suffi cient power from
inverter.
LEDs and
Remote may be
backlight are
in the Power Save
off
mode.
Remote is
Communication
non-functional
cable bad or not
(no lights, no
correctly connected
text on LCD
to remote port on
display, and no
inverter.
response when
pressing any
button)
Inverter is not
connected to
batteries.
62
Solution
Refresh Display: press and
hold the SELECT knob for 10
seconds.
Reset remote: 1) Disconnect
remote cable from inverter for
5 seconds and reconnect; 2)
Check RJ11 cable connection on
back of remote (see Figure 2-2).
Important: Ensure the RJ11
connector is pushed into
the correct port. You should
feel/hear a "click" when the
connection is made.
Ensure inverter batteries are
connected and inverter is
operating correctly; inverter
should be able to invert and
power AC loads from batteries
(ensure no AC power is
connected to the inverter AC
inputs).
Press any button to reactivate
the remote (or turn Power Save
mode Off).
Check communications cable
from inverter to remote;
ensure: 1) it is connected to
the REMOTE port, 2) the correct
communications cable is used
(a 4-conductor telephone
cable may be substituted to
determine if cable is good).
Ensure inverter batteries are
connected and the inverter
is operating correctly without
any AC power connected (can
invert and power AC loads from
batteries).
© 2012 Magnum Energy, Inc.