Ags Remote Fault Statuses; Table 7-4, Ags Remote Fault Statuses; Table 7-5, Ags Default Settings On Me-Arc - Magnum Energy ME-ARC Series Owner's Manual

Advanced remote control
Hide thumbs Also See for ME-ARC Series:
Table of Contents

Advertisement

7.0 Using an AGS Module

7.7.3 AGS Remote Fault Statuses

The following "Fault" statuses indicate that the generator wasn't able to start
based on an expected autostart condition. Refer to
AGS Faults Using the Remote" for help in diagnosing the problem.

Table 7-4, AGS Remote Fault Statuses

STATUS
Gen Run Fault
The generator successfully started and ran for more than
two minutes, but unexpectedly stopped before the AGS
could automatically stop the generator.
Fault Amp
The generator failed to start in Start Amps mode.
Fault Exercise
The generator failed to start in Start Exercise mode.
Fault SOC
The generator failed to start in Start SOC mode.
Fault Temp
The generator failed to start in Start Temp mode.
Fault Test
The generator failed to start in Test mode.
Fault Time
The generator failed to start in Start Time mode.
Fault Topoff
The generator failed to start in Start Topoff mode.
Fault VDC
The generator failed to start in Start VDC mode.
Fault MaxRn
The generator turned off because the SETUP: 04F Max
Gen Run Time setting had been met. This fault can occur
when: 1) an autostop parameter has been met, but it
did not stop the generator, or, 2) the autostop condition
exceeded the Max Gen Run Time setting.

Table 7-5, AGS Default Settings on ME-ARC

Menu Items
Gen Run VDC
Gen Run Time
Gen Run Amps*
Gen Run SOC
Gen Run Temp
Max Gen Run Time
Quiet Time
Gen Exercise
Gen Warm-up Time
Gen Cooldown Time
*MS-PAE, MS-PE and MSH Series models only
88
Section 7.8.3
DESCRIPTION
Default Settings
Start Volts: 11.5 VDC (12v)
Start Volts Delay: 120 Sec
Stop Volts: 14.4 VDC (12v)
Stop Volts Delay: 120 Sec
OFF
OFF
OFF
OFF
12.0 Hrs
OFF
OFF
60 Sec
60 Sec
© 2012 Magnum Energy, Inc.